NYT Printing Facility

IPMVP Option B Readiness — Building Summary
Coating Readiness Need More Data
EER Coverage iOf all compressor-on readings, how many have valid EER values. High-OA units naturally have lower coverage because when supply air enthalpy ≤ outdoor enthalpy at moderate OAT, EER is physically undefined (no net cooling). This is expected physics, not a data problem. 88,401/94,063 (94.0%)
Max OAT Observed iHighest outdoor air temperature recorded during compressor-on operation. Coating baseline needs 90°F+ readings to capture peak-load performance. 92.1°F
Weather Feed iStatus of Open-Meteo weather data for this site. Weather data is needed for EER pairing and OAT bin regression. 0h ago
• Baseline at 88% — close to ready, keep collecting.
OAT Bin Performance
Bin (°F) Readings Avg kW Avg EER
60–65° 12,904
24.1 16.2
65–70° 16,728
27.6 14.5
70–75° 17,942
30.0 14.0
75–80° 18,507
34.5 12.5
80–85° 9,565
33.0 9.8
85–90° 8,992
36.2 8.3
90–95° 2,767
40.0 7.7
95–100° 0
NYT Printing Facility (2 units) 88% Partial
OAT Bin Coverage iNeed ≥5 of the 8 five-degree bins (60–100°F) with compressor-on readings. Filled: 60–65°F, 65–70°F, 70–75°F, 75–80°F, 80–85°F, 85–90°F, 90–95°F. Empty: 95–100°F. 7/5 bins Passed. Still empty: 95–100°F.
Min Readings/Bin iStatistical power per temperature bin. The thinnest filled bin must have at least 10 readings for a defensible average. 2767/10 readings
Total Readings iTotal compressor-on readings with valid OAT. Larger datasets produce tighter regression confidence intervals. Target: 500+. 94063/500 readings
Monitoring Window iCalendar days from first to last compressor-on reading. At least 14 days captures weekday/weekend cycles and weather variation. 40.4/14d
kW-vs-OAT R² iHow strongly outdoor temperature predicts electrical power draw (linear regression). R² ≥ 0.75 means OAT explains at least 75% of kW variance. 0.33/0.75 Moderate correlation. More temperature variation may improve fit.
Diagnostics
Data Completeness iOf all the readings the sensor should have sent (based on its reporting interval), how many actually arrived? Small gaps from WiFi hiccups are normal. Only a concern if large chunks of time are missing. 52.6% Significant data gaps (47.4% missing). Verify sensor is online and gateway has stable connection.
CV-RMSE iCoefficient of Variation of RMSE — measures how well the kW-vs-OAT regression fits the data. Lower is better: <15% excellent, <25% good, 25%+ may need more data or a non-linear model. 22.9% good
Sensor Channels iAll mapped sensor channels should have at least one reading. Missing channels may indicate dead sensors or configuration errors. 10/10
Regression Model iBaseline regression equation: kW = slope × OAT + intercept. Required by IPMVP for 3rd-party verification of the baseline model. kW = 0.6126 × OAT + -12.50
EER Model iEER vs OAT regression. A positive slope is expected physics for high-OA units: higher outdoor temp → higher cooling load → more efficient compressor operation (closer to design conditions). Negative slope is typical for recirculation-dominant units. EER = 0.1213 × OAT + 5.30 (R²=0.060)
NMBE iNormalized Mean Bias Error — measures systematic over/under-prediction. IPMVP threshold: <±5% excellent, <±10% acceptable. -0.0% excellent
Durbin-Watson iTests whether regression residuals are independent over time. DW ≈ 2.0 = good. DW < 1.5 = positive autocorrelation (model misses a trend). DW > 2.5 = negative autocorrelation. 1.32 caution
Sensor Status
Sensor ID Unit Measures Source Readings Interval Data From Last Seen Status
1359851 ACU-12 amperage monnit 61,209 ~60s 2026-03-24 2026-05-06 06:31:46 Healthy
1360126 ACU-12 condenser_outlet_temp monnit 60,572 ~60s 2026-03-26 2026-05-06 06:31:33 Healthy
1326796 ACU-12 discharge_temp monnit 60,560 ~60s 2026-03-26 2026-05-06 06:31:12 Healthy
1324388 ACU-12 evap_inlet_rh monnit 58,673 2026-03-23 2026-05-02 18:10:37 Healthy
1324371 ACU-12 evap_outlet_rh monnit 61,436 ~60s 2026-03-23 2026-05-06 06:31:52 Healthy
1359837 ACU-14 amperage monnit 60,796 ~60s 2026-03-26 2026-05-06 06:31:18 Healthy
1376476 ACU-14 condenser_outlet_temp monnit 60,532 ~60s 2026-03-26 2026-05-06 06:31:06 Healthy
1376472 ACU-14 discharge_temp monnit 60,532 ~60s 2026-03-26 2026-05-06 06:31:24 Healthy
1352602 ACU-14 evap_inlet_rh monnit 60,539 ~60s 2026-03-26 2026-05-06 06:31:50 Healthy
1352393 ACU-14 evap_outlet_rh monnit 60,514 ~60s 2026-03-26 2026-05-06 06:31:22 Healthy
Site Total 605,363 2026-03-23 2026-05-06 06:31:52
Drop iMonnit gateway screenshot to import sensors
or click to browse — AI extracts sensor IDs, names & types
Per-Unit Summary
Unit Tons Install Age Avg EER Avg kW Est. EFLH Latent % Subcool ΔT Readiness Status
ACU-12 90T 1996 30yr Collecting
ACU-14 150T 1996 30yr Collecting
Live Readings
|
EER vs Outdoor Temp
% Load vs Outdoor Temp
EER (BTU/W)
Amperage
kW
Evap Coil Temps (Inlet / Outlet)
Enthalpy Delta
Cooling Breakdown (Sensible + Latent)
Latent Cooling Fraction (%)
Discharge → Outlet Delta
Condenser Temps (Discharge / Outlet)