ACU Fleet (29 units coated) — Unit by Unit Export Data M&V Library The Refinery

Unit by Unit

NYT Printing Facility, Queens NY | AHU — Mammoth Tier 1
ACU-11 ACU-14 ACU-10 ACU-12

ACU-10 150T Partial Data

150-ton Mammoth AHU. Post-treatment only (Jul-Sep 2016 hourly data). No pre-treatment raw data — cannot compute improvement from raw data. 9-year persistence EER available.

Data Conflict — Two Different EER Baselines

2016 Savings Summary (xlsx): EER pre 3.2 → post 8.4 (+163%)
Avg EER across all hours including low-load. Likely includes off/cycling readings.
Persistence CSV (2024): EER pre 8.73 → post 9.91 (+13.2%)
Genuine measured EER at representative operating conditions. 9-year value 9.89 (0.2% degradation).
Post-Treatment Performance Profile
Post-treatment readings Outdoor temp (right axis) No pre-treatment data available for this unit
Data Window

Post-Treatment (Only Available Period)

Readings
366
2016-07-14 → 2016-09-06
Avg EER7.04 Btu/Wh
Avg Power37.24 kW
Persistence (EER)

9-Year EER Persistence

From persistence study (not OAT-binned raw data). Single measured EER data points.

8.73
EER Pre (2016)
9.91
EER Post (2016)
9.89
EER 9-Year (2024)
0.2%
Degradation
IPMVP Compliance
Insufficient IPMVP Option B · Retrofit Isolation
0
OAT Bins
0 / 366
Readings Pre / Post
0 / 54
Window (days)

Post-treatment data only — no pre-treatment baseline.

Measurement Details

Dataset Metadata

Resolution1 hour
TimezoneAmerica/New_York
Total Readings366
Post-treatment Window2016-07-14 – 2016-09-06
Tonnage150T

Measured Fields

FieldLabelUnit
outdoor_temp_f Outdoor Temp °F
total_kw Total Power kW
eer EER Btu/Wh
tons Tons tons
Download post CSV