ACU Fleet (29 units coated) — Inputs Export Data M&V Library The Refinery

Inputs

NYT Printing Facility, Queens NY | 29 units • 3475T total
Inputs & Assumptions
Parameter Value Source Note
EER Pre/Post (ACU-11) 8.93 / 11.34 verified Independent psychrometric calc, 10k CFM, same-season
EER Improvement (ACU-11) 28.3% verified Weighted avg across 2 OAT bins (57.5°F, 62.5°F)
9-yr Persistence (ACU-11) -3.85% kW verified vs 2016 post, NOAA KLGA-validated OAT
10-yr Persistence (ACU-14) -31.5% comp kW verified vs 2015 pre, Monnit comp-only CT, shoulder-to-shoulder
Treatment Date Nov 2015 from report 29 AHU evaporator coils
Equipment Mammoth AHUs (90-150T) from report Vintage 1996
ACU-11 CFM 10,000 back calculated From vendor enthalpy/Tons data
ACU-14 CFM 32,000 back calculated From vendor enthalpy/Tons data
Voltage 480V 3φ from report PF=0.85
EFLH 2,000 hrs assumed NYC climate zone
Utility Rate $0.15/kWh assumed Con Edison commercial